The photographs show the bare FKN load-switch structure. FKRN models are separate load-switch/fuse combinations.

Indoor switching · load break switch

FKN12-12Indoor air-blast load break switch

An indoor 12 kV AC air-blast load break switch for medium-voltage distribution equipment. The ratings below are for FKN12-12D/630-20. Confirm the grounding-switch option, operating method, mounting direction, operating side and supply for your order.

Rated voltage
12 kV
Rated frequency
50 Hz
Rated current
630 A
Short-time withstand
20 kA

For FKN12-12D/630-20, 20 kA is the rated short-time withstand current. It is not a short-circuit breaking rating.

Complete product ratings

FKN12-12D/630-20 specifications.

These ratings apply to the bare FKN12-12D/630-20 load switch. Other FKN12 order codes may differ; FKRN load-switch/fuse combination ratings are separate.

Electrical ratings · FKN12-12D/630-20
No.ParameterUnitValue
01Rated voltagekV12
02Rated frequencyHz50
03Rated currentA630
04Rated short-time withstand current, load switchkA20
05Rated short-time withstand duration, load switchs4
06Rated short-time withstand current, grounding switchkA20
07Rated short-time withstand duration, grounding switchs2
08Rated short-circuit making current (dynamic stability current)kA50
09Power-frequency withstand voltage, 1 min, phase-to-earth / phase-to-phasekV42
10Power-frequency withstand voltage, 1 min, across open contactskV48
11Lightning-impulse withstand voltage (peak), phase-to-earth / phase-to-phasekV75
12Lightning-impulse withstand voltage (peak), across open contactskV85
13Rated active-load breaking currentA630
14Rated closed-loop breaking currentA630
15Rated 5% active-load breaking currentA31.5
16Rated cable-charging breaking currentA10
17Rated no-load transformer breaking capacitykVA1600
18Mechanical enduranceoperations5000
Mechanical characteristics · FKN12-12D/630-20
No.ParameterUnitValue
01Contact opening distancemm≥175
02Phase-center distancemm210 ± 2
03Air clearance from live parts to groundmm≥125
04Moving-contact travelmm210 ± 4
05Moving-contact overtravelmm≥40
06Closing speedm/s≥2.5
07Opening speedm/s≥2.5
08Three-phase closing asynchronismms≤5
09Three-phase opening asynchronismms≤5
10Shunt-release permanent opening timems≤65
11Main-circuit resistanceµΩ≤150
12Operating torqueN·m≤200
Normal service conditions
No.ConditionUnitValue
01Ambient temperature°C−25 to +40
02Altitudem≤2,000
03Relative humidity%Daily average ≤95; monthly average ≤90
04Seismic intensitydegrees≤8
05Pollution degree—II
06Atmosphere—No corrosive or combustible gas, steam or other stated contamination.

For FKN12-12D/630-20, 20 kA is the rated short-time withstand current; it is not a short-circuit breaking rating. The FKN12-12/630-20 code omits the grounding-switch suffix. The ratings above apply to FKN12-12D/630-20.

Mounting and operating options.

Normal and inverted installation are available. Match the cabinet dimensions, operating direction and secondary circuits to the approved drawings.

Normal and inverted installation

ArrangementMechanical and primary fitControl and interlocks
Normal installation Side-operated. Confirm mounting points, cable entry, clearances and left- or right-hand operating direction against the cabinet drawing. If a grounding switch is selected, its side must be opposite the incoming-line side. Confirm the interlock arrangement for the selected configuration.
Inverted installation For bottom cable entry, specify inverted installation. Check mounting points and primary clearances against the approved cabinet drawing. Keep the grounding-switch side opposite the incoming line. Confirm the interlock geometry and control wiring for the order.

For a 900 mm cabinet depth, the listed defaults are 194 mm from the panel to the mounting hole and 494 mm from the panel to the B-phase center. Confirm dimensions against the approved order drawing; other dimensions may be specified.

Model and operating side

Bare-switch codes: FKN12-12/630-20 or FKN12-12D/630-20. The D suffix identifies the grounding-switch option; the detailed ratings on this page apply to FKN12-12D/630-20.

Product type: FKN is the bare load switch; FKRN is the separate load-switch/fuse combination.

Operating side: specify left- or right-hand operation.

Mechanism and control supply

Mechanism: manual, electric, or manual closing with electric tripping. Manual closing with electric tripping is available with AC or DC control power.

Supply: select 110 V or 220 V AC or DC. The default is AC 220 V; electric AC and DC versions are not interchangeable.

Other options: specify auxiliary-contact quantity, grounding microswitch, electromagnetic lock, back-to-back interlock, live-voltage indicator or program lock.

Auxiliary-contact and grounding-switch defaults

Operating mechanismAuxiliary contacts fittedConnected to terminal blockGrounding microswitch
Manual None No auxiliary wiring None
Manual closing with electric tripping 2 NO + 3 NC 2 NO + 2 NC None
Electric 4 NO + 5 NC 2 NO + 2 NC 1 NO provided; not connected

NO means normally open; NC means normally closed. Confirm the terminal schedule for the specified configuration.

FKN12 · Layout drawings

Left- and right-hand installation drawings.

Compare the mounting layout for the selected operating side. Dimensions are for reference; confirm clearances and interfaces against the approved order drawing.

Select an operating-side reference

FKN12 drawing reference

FKN12 right-hand operating layout

Open manual at PDF page 8
FKN12-12 right-hand operating and installation-dimension drawing.
Right-hand operating arrangement.

FKN12 drawing reference

FKN12 left-hand operating layout

Open manual at PDF page 8
FKN12-12 left-hand operating and installation-dimension drawing.
Left-hand operating arrangement.

These mechanical drawings show the installation layout. A separate CAD file and an FKN12-specific control wiring diagram are not available here. Use the approved project drawings for mounting points, clearances and control connections.

Manual, selection form and test report.

Use the manual and selection form for the selected FKN or FKRN configuration; the test report covers the named FKRN sample.

Available · PDF · 8 pages

FKN12-12(D) installation and operation manual

Operation, installation, ratings and outline drawings for the FKN load switch and FKRN fuse combination, with separate data for each product type.

Open manual PDF

Available · DOC

FKN12-12 selection form

Record the model, mounting direction, operating side, mechanism, supply, cabinet interface, auxiliary contacts and options for your order.

Download selection form

Available · PDF · 46 pages

FKRN12-12D/125-31.5 type-test report

Report 2013345856, dated 16 November 2020, lists nine test categories for one 12 kV, 125 A, 31.5 kA FKRN load-switch/fuse combination sample, including combined making/interruption, tripping coordination, fuse vibration and temperature rise. This scope does not cover the standalone FKN12-12D/630-20 load switch.

Open sample report

See Liqiang manufacturing and inspection activities. Model reports and factory inspection records serve different purposes; match the required documents to the proposed equipment.

Price & quotation.

Configuration · FKN12-12 630 A

FKN12-12 630 A air-blast load break switch

Price reference for the specified FKN12-12 630 A configuration. Base 630 A switch configuration. Fuse combination, earthing arrangement and operating accessories must be confirmed separately.

Rated voltage
12 kV
Rated current
630 A
Arc-quenching system
Air-blast

Price range

USD 275–280 / set

USD per complete three-phase set. Minimum order: 1 set. USD 280 per set for 1–49 sets; USD 275 per set for 50+ sets. Shipping and taxes are excluded. Other configurations and accessories require a separate quotation. Confirm the specification and final quotation before ordering.

The range reflects order-quantity tiers for this configuration; it does not cover every option in the series.

Quantity pricing
Published quantity tiers for this configuration
Quantity (sets)Price per set
1–49USD 280
50+USD 275

FKN12 selection questions.

Answers for choosing the switch, installation arrangement and supporting documents.

01What is the difference between FKN12 and FKRN12?

FKN identifies the bare load switch. The R in FKRN identifies the separate load-switch/fuse combination. Select current and fault-duty ratings for the exact model; see the FKN12 ratings above.

02Does 20 kA mean the FKN12 switch interrupts a 20 kA fault?

No. For FKN12-12D/630-20, 20 kA is the rated short-time withstand current. It does not mean the switch has a 20 kA short-circuit breaking capacity. See the ratings above.

03What mechanism and operating supply can be specified?

Available mechanisms include manual, electric, and manual close/electric trip. Supply options include AC or DC at 110 V or 220 V. Confirm a compatible mechanism and supply in the configuration options.

04When should I select an FKRN12 switch-fuse combination?

Select the switch-fuse arrangement when the circuit design calls for load switching together with coordinated fuse protection, such as a transformer feeder. Specify transformer power, system voltage, fault level and the fuse/striker arrangement. Use the complete FKRN12 designation when discussing the switch and fuse configuration.

05Which dimensions are needed for an FKN12 cabinet layout?

Provide the cabinet outline, mounting points, terminal positions and operating space. Identify left- or right-hand operation, mechanism position and the earthing arrangement. Compare these interfaces with the installation drawings and use the approved order drawing for cabinet fabrication.

06What details are needed for a quotation?

Provide the full FKN/FKRN model code, grounding-switch option, rated duty, mounting direction, operating side, mechanism and supply, cabinet interface, auxiliary-contact count, and required locks or interlocks. Attach cabinet-outline and primary/control drawings when available. The selection form lists the available options.

Product engineering series

About Liqiang

Manufacturing and technical support.

Technical selection guide