Indoor load switches · 12 kV series

FZN25Indoor AC vacuum load switch

Three-pole assembly and single-pole module views. Confirm the selected earthing and operating arrangement against the approved order drawing.

An indoor three-phase vacuum load switch for 12 kV, 50 Hz distribution equipment. The ratings below apply to FZN25-12D/630-20. Confirm the earthing arrangement, operating method and cabinet interfaces for your order.

Rated voltage
12 kV
Rated frequency
50 Hz
Rated current
630 A
Short-time withstand
20 kA
Peak withstand / making
50 kA

Confirm short-circuit protection for the selected assembly. FZRN25 switch-fuse combination ratings are separate.

Review all electrical and mechanical data

FZN25 technical specifications.

Ratings for FZN25-12D/630-20. Check the selected operating mechanism, control supply and service conditions before specifying the assembly.

Electrical ratings — FZN25-12D/630-20
No. Item Unit Value
01 Rated voltage kV 12
02 Rated frequency Hz 50
03 Rated current A 630
04 Rated active-load breaking current A 630
05 Rated closed-loop breaking current A 630
06 No-load transformer switching capacity kVA 1,600
07 Rated cable-charging breaking current A 10
08 Rated transfer current A —
09 Rated short-time withstand current kA 20
10 Rated peak withstand current kA 50
11 Rated short-circuit breaking current kA —
12 Rated short-circuit making current kA 50
13 Power-frequency withstand voltage, 1 min (phase-to-phase and earth / isolating gap) kV 42 / 48
14 Lightning-impulse withstand voltage, peak (phase-to-phase and earth / isolating gap) kV 75 / 78

A dash means no rating is specified for this configuration. Do not apply FZRN25 switch-fuse combination ratings to FZN25. Confirm the exact /630-20 or /T630-20 order designation on the approved drawing.

Mechanical and operating data

Mechanical characteristics
No. Item Unit Value
01 Vacuum interrupter opening contact gap mm 6 +1 / −0
02 Vacuum interrupter contact compression travel mm 2 +1 / −0
03 Isolating opening gap mm ≥ 130
04 Phase-center distance mm 210 ± 1
05 Three-phase opening / closing asynchronism ms ≤ 3
06 Contact bounce at closing ms ≤ 3
07 Average closing speed m/s 0.6 ± 0.2
08 Average opening speed m/s 0.9 ± 0.2
09 Per-pole conductive circuit resistance µΩ ≤ 180
10 Maximum manual operating torque N·m ≤ 160
11 Mechanical life operations 10,000
Motor and shunt trip ratings
Item Rated voltage / current Rated output Normal working-voltage range
AC/DC 220 V motor 0.7 A 90 W 85%–110% of rated voltage
AC/DC 110 V motor 1.5 A 90 W 85%–110% of rated voltage
Shunt trip coil AC/DC 220 V / 110 V 968 W 65%–110% of rated voltage

Service conditions

Service conditions
No. Item Unit Value
01 Ambient temperature °C −25 to +40
02 Relative humidity, daily average % ≤ 95
03 Relative humidity, monthly average % ≤ 90
04 Altitude m ≤ 2,000
05 Seismic intensity degree < 8
06 Surrounding-air contamination — No contamination by corrosive or flammable gases or harmful vapours
07 Pollution degree — II

Confirm the selected model and installation environment. Projects outside these service conditions require an agreed specification.

Mounting and control options.

Normal and inverted mounting are available. Match the earthing arrangement, cabinet dimensions, operating side and control wiring to the approved order drawings.

Normal and inverted installation

Arrangement Mechanical and primary fit Control and interlocks
Normal installation Side-operated. Confirm the mounting points, cable entry, primary clearances and operating side against the cabinet layout. When an earthing switch is selected, its side must not be the incoming-line side. Confirm the mechanical and electrical interlocks for the order.
Inverted installation Select inverted installation for bottom cable entry when an earthing switch is fitted. Check mounting points and clearances against the approved layout. Keep the earthing-switch side away from the incoming line. Confirm the selected operating side and interlock arrangement.

For a 900 mm cabinet depth, the standard interface dimensions are 175 mm from the panel to the mounting hole and 495 mm from the panel to the B-phase centre. Confirm these dimensions on the approved order drawing; other dimensions must be specified.

Model and operating side

Load-switch codes: FZN25-12/630-20 or FZN25-12D/630-20. The D version includes an earthing switch. The detailed ratings on this page apply to FZN25-12D/630-20; confirm the ratings separately for a non-D order.

Operating side: specify left- or right-hand side operation.

Product type: FZRN25 is a separate switch-fuse combination with different ratings.

Mechanism and control supply

Mechanism: manual, motor-operated, or manual closing with electric tripping. The manual version has no auxiliary contacts or wiring; manual closing with electric tripping accepts AC or DC control power.

Supply: specify 110 V or 220 V AC or DC. The standard supply is AC 220 V; AC and DC motor versions are not interchangeable.

Closing circuit: specify whether closing self-hold is required. The standard circuit has no relay self-hold function.

Other options: specify a voltage sensor, electromagnetic lock, back-to-back interlock, live-voltage indicator or program lock. The voltage sensor is omitted as standard.

Auxiliary-contact and earthing-switch defaults

Mechanism Auxiliary contacts available Connected to terminal block Earthing microswitch
Manual closing with electric tripping 2 NO + 3 NC 2 NO + 2 NC None
Motor-operated 4 NO + 3 NC 2 NO + 1 NC 2 NO; not connected to the terminal block

NO = normally open; NC = normally closed. Confirm the required contact count, terminal allocation and earthing microswitch wiring on the final terminal schedule.

FZN25 dimensions and wiring.

Compare the front outline and motor-control functions with your cabinet layout. Confirm final mounting dimensions, control supply and terminal allocation on the approved order drawings.

Choose a drawing reference

Front outline with phase spacing, mounting holes and dimension lines for the illustrated FZN25/FZRN25 arrangement.

Front outline

Dimensions in mm for the illustrated FZN25/FZRN25 family arrangement. Check phase spacing, mounting holes, clearances and the operating-side interface for the selected assembly.

Mechanism thickness depends on the cabinet design. Use the approved order drawing for final installation dimensions.

Open full drawing at PDF page 7

Motor-control circuit with original terminal numbers and QF, DX1, DX2, M, TQ and S symbols.

Motor control circuit

Terminal functions
Terminals Function
1–2 Energy storage / closing
7–8 Opening circuit
3–4 / 5–6 Auxiliary signals
11–12 / 9–10 Closing-hold connections in the user circuit

The load switch and earthing switch are shown open, with the interlock closed. Two NO and two NC contacts are reserved and not connected to the terminal block in this reference.

Confirm the control supply, contact allocation and final wiring for the selected assembly. This reference does not replace its terminal schedule.

Open full circuit at PDF page 6

FZN25 manual and selection form.

The manual provides ratings and installation guidance. Use the selection form to specify the switch and operating options for your order.

Available · PDF · 7 pages

FZN25 / FZRN25 installation manual

Model codes, ratings, operation and installation drawings for FZN25 load switches and FZRN25 switch-fuse combinations. Match the selected model and configuration before use.

Open manual PDF

Available · DOC · 1 page

FZN25 / FZRN25 selection form

Specify the model, earthing option, mounting arrangement, operating side, mechanism, control supply, auxiliary contacts and interlocks.

Download selection form

Price & quotation.

Configuration · FZN25-12 630 A

FZN25-12 630 A vacuum load switch

Price reference for the specified FZN25-12 630 A configuration. Base 630 A switch configuration. FZRN fuse combinations and selected fuse links are quoted separately.

Rated voltage
12 kV
Rated current
630 A
Arc-quenching system
Vacuum

Price range

USD 275–280 / set

USD per complete three-phase set. Minimum order: 1 set. USD 280 per set for 1–49 sets; USD 275 per set for 50+ sets. Shipping and taxes are excluded. Other configurations and accessories require a separate quotation. Confirm the specification and final quotation before ordering.

The range reflects order-quantity tiers for this configuration; it does not cover every option in the series.

Quantity pricing
Published quantity tiers for this configuration
Quantity (sets) Price per set
1–49 USD 280
50+ USD 275

FZN25 selection questions.

Answers to common questions about earthing, protection, controls and installation.

01Does FZN25 include an earthing switch?

The FZN25-12D version includes an earthing switch. Specify the D or non-D arrangement when ordering. The detailed ratings on this page apply to FZN25-12D/630-20; confirm ratings separately for a non-D assembly. See the configuration options.

02Is 20 kA a short-circuit breaking rating?

No. For FZN25-12D/630-20, 20 kA is the short-time withstand rating. No short-circuit breaking rating is specified here. Confirm short-circuit protection for the selected assembly; FZRN25 switch-fuse combination ratings are separate. See the complete ratings.

03Can AC and DC motor versions be interchanged?

No. Specify 110 V or 220 V AC or DC for the motor-operated version; the standard supply is AC 220 V. Manual closing with electric tripping accepts AC or DC control power. Confirm the selected supply and final circuit in the control requirements.

04Can I install directly from these drawings?

Use them as references for the illustrated family arrangement. Final dimensions, mechanism thickness, earthing position, cabinet fit and terminal allocation must follow the approved order drawings. See the outline and circuit references.

05What should I specify in an order?

Confirm the model, quantity, earthing option, mounting arrangement, cable entry, operating side, mechanism, control supply, auxiliary contacts and interlocks. Complete the selection form with these requirements.

Product engineering series