Indoor load switches · 12 kV series

VZF-12 / VZFR-12Solid-sealed vacuum load switches

Images show the VZFR-12 switch-fuse combination. Confirm the selected arrangement and cabinet fit against the approved order drawing.

An indoor vacuum load-switch family for 12 kV distribution cabinets. Select the VZF-12 bare load switch or VZFR-12 switch-fuse combination, then specify the mechanism, control supply and cabinet interfaces for your order.

Rated voltage
12 kV
Fuse rated current
160 A
Fuse breaking current
50 kA
Power-frequency / impulse withstand
42 / 75 kV
Rated transfer current
3,150 A
Electrical life
10,000 operations

Ratings shown apply to VZFR-12/T160-50. Confirm the complete rating schedule for the bare VZF-12 switch and other combinations.

VZF / VZFR-12 technical specifications.

Electrical ratings below apply to the VZFR-12/T160-50 switch-fuse combination. Confirm a separate rating schedule for the bare VZF-12 load switch or another combination before selecting the assembly.

Electrical ratings — VZFR-12/T160-50
No.ItemUnitValue
01Rated voltagekV12
02Power-frequency withstand voltage, phase-to-phase and phase-to-earthkV42
03Lightning-impulse withstand voltage, phase-to-phase and phase-to-earthkV75
04Fuse rated currentA160
05Fuse rated short-circuit breaking currentkA50
06Rated short-time withstand currentkA—
07Rated peak withstand currentkA—
08Rated short-circuit closing currentkA—
09Rated cable-charging breaking currentA—
10Rated transfer currentA3150
11No-load transformer switching capacitykVA1250
12Electrical lifeoperations10000
13Partial dischargepC≤5

The 160 A current and 50 kA breaking capacity are fuse ratings. A dash means no applicable value is specified for this combination; it does not indicate zero capacity or a bare-switch rating.

Mechanical characteristics

Mechanical characteristics — VZFR-12
No.ItemUnitValue
01Contact opening distancemm8–10
02Contact-pressure spring travelmm3–5
03Phase-center distancemm150 / 210 / 275
04Three-phase closing/opening asynchronismms≤2
05Contact closing bouncems≤3
06Average closing speedm/s0.4–0.8
07Average opening speedm/s1.0–1.4
08Closing time at rated operating voltagems≤60
09Opening time at rated operating voltagems≤30
10Main-circuit resistanceµΩ≤250
11Moving/static contact wear allowancemm3

Operating mechanism

Spring mechanism and charging motor
No.ItemUnitValue
01Closing interlock electromagnet Y1VA/W3
02First shunt release Y2 — standardVA/W220
03Closing release Y3 — standardVA/W220
04Overcurrent releases Y7–Y9 — optionalVA/W—
05Undervoltage release Y4 — optionalVA/W—
06Truck interlock electromagnet Y0 — optionalVA/W3
07Spring-charging motor rated voltageVAC 220 / 110; DC 220 / 110
08Spring-charging motor powerW90
09Spring-charging times≤8

VA/W denotes AC apparent power or DC power. Optional overcurrent and undervoltage release ratings require confirmation. Select the mechanism supply and optional devices together with the final control circuit.

Service conditions

Normal service conditions
No.ItemUnitValue
01Ambient temperature°C−25 to +40
02Relative humidity, daily average%≤95
03Relative humidity, monthly average%≤90
04Saturated water-vapour pressure, daily averageMPa≤2.2 × 10⁻³
05Saturated water-vapour pressure, monthly averageMPa≤1.8 × 10⁻³
06Altitudem≤1500
07Seismic intensitydegree≤8
08Location—No dripping water, fire or explosion hazard, chemically corrosive gas or severe vibration

Installations outside these conditions require an agreed specification.

Load switch and fuse-combination options.

Choose the bare load switch or switch-fuse combination first. Then specify the truck fit, fuse arrangement, operating supply and auxiliary circuits for the complete order.

VZF and VZFR assemblies

AssemblyMechanical and primary fitControl and interlocks
VZF-12 bare load switchConfirm the truck, primary contacts, cabinet dimensions and clearances for the selected load-switch assembly.Specify the spring mechanism, operating supply and auxiliary circuits. Confirm closing and truck interlocks on the approved schematic.
VZFR-12 switch-fuse combinationWithdrawable truck with solid-sealed poles and top-mounted fuses. Match the cabinet width, phase-centre spacing, pole spacing and fuse dimensions to the selected assembly.Coordinate the fuse, striker and tripping arrangement. Check fuse-operation indication and the final control circuit against the approved schematic.

The detailed electrical ratings on this page cover VZFR-12/T160-50 only. Confirm separate ratings for a bare VZF-12 switch or another combination; fuse breaking ratings do not establish the bare switch’s short-circuit duty.

Cabinet and fuse fit
  • Cabinet width: 650 / 800 / 1,000 mm; the usual selection is 800 mm. Confirm the complete layout for the selected assembly.
  • Phase-centre spacing: 150 / 210 / 275 mm; usual 210 mm. Specify pole spacing separately: 275 / 310 mm, usual 275 mm.
  • Fuses, combination only: specify the coordinated type, rated current and breaking duty. The selection dimensions are a 360 mm core length and Ø45 mm end diameter; confirm the complete fuse and holder before ordering.
Mechanism and control supply
  • Mechanism: spring-operated, with a 90 W charging motor and charging time ≤8 s.
  • Supply: 110 or 220 V AC or DC; the usual voltage is 220 V. Confirm the actual control and motor supply with the final circuit.
  • Interlocks: anti-pumping is standard. Closing and truck locks are optional and are omitted from the standard selection.
  • Other options: extended truck handle, undervoltage release and program lock with 2 locks / 1 key or 3 locks / 2 keys. Confirm each required option in the order.

Auxiliary contacts

CircuitStandard reservation
Auxiliary switch4 NO + 4 NC
Energy-storage indication2 NO + 1 NC

NO = normally open; NC = normally closed. Confirm the supplied contacts and terminal allocation against the approved wiring drawing.

VZFR-12 outline dimensions.

The side profile shows height and front-to-back clearances. Use the cabinet-width schedule with the complete front view when finalizing the cabinet layout.

Side-profile dimensions

Open full-size drawing
VZFR-12 side-profile dimensions for the withdrawable switch-fuse combination, with dimensions in millimetres.

VZFR-12 switch-fuse combination side profile. Dimensions are in mm. Use the complete outline for front-view dimensions and operating-panel markings.

Open complete outline at PDF page 6

Cabinet-width dimensional schedule

VZFR-12 cabinet dimensions and weight
Cabinet widthPABCEWeight
650 mm150 mm500 mm530 mm490 mm203 mm120 kg
800 mm210 mm650 mm680 mm640 mm278 mm140 kg
1000 mm275 mm850 mm880 mm840 mm378 mm160 kg

P, A, B, C and E correspond to the lettered dimensions in the complete front view. Check the selected cabinet width and phase spacing together; these values do not establish dimensional compatibility for the bare VZF-12 switch.

Open dimensional schedule at PDF page 7

Confirm all interfaces on the approved order drawing. Cabinet layouts and secondary wiring require the project drawings; standalone CAD files are not included in these downloads.

VZF / VZFR-12 manual and selection form.

The manual covers the switch and fuse-combination assemblies. Use the selection form to specify cabinet dimensions and control requirements.

Available · PDF · 12 pages

VZF / VZFR-12 product manual

Family designations, VZFR-12 ratings, operating mechanism, service conditions and cabinet outlines. The detailed electrical rating example is VZFR-12/T160-50; confirm the complete order code before use.

Open manual PDF

Available · DOC · 1 page

VZF(R)-12 selection form

Specify the product branch, cabinet width, phase and pole spacing, fuse, operating supply, contacts and accessories. Confirm the model designation and rating schedule for the requested assembly.

Download selection form

Price & quotation.

Configuration · VZF-12 630 A

VZF-12 630 A vacuum load switch

Price reference for the specified VZF-12 630 A configuration. VZF-12 630 A configuration only. This is not the price of the VZFR-12/T160-50 fuse combination.

Rated voltage
12 kV
Rated current
630 A
Quoted model
VZF-12

Price range

USD 980–1000 / set

USD per complete three-phase set. Minimum order: 1 set. USD 1000 per set for 1–99 sets; USD 980 per set for 100+ sets. Shipping and taxes are excluded. Other configurations and accessories require a separate quotation. Confirm the specification and final quotation before ordering.

The range reflects order-quantity tiers for this configuration; it does not cover every option in the series.

Quantity pricing
Published quantity tiers for this configuration
Quantity (sets)Price per set
1–99USD 1000
100+USD 980

Selection questions.

Answers about VZF-12 and VZFR-12 assemblies, cabinet fit, controls and product files.

01How do VZF-12 and VZFR-12 differ?

VZF-12 is the bare vacuum load switch; VZFR-12 is the load-switch/fuse combination. The product views show the VZFR-12 combination. Confirm the selected assembly in the configuration requirements.

02Does the 50 kA rating apply to a bare VZF-12 switch?

No. The 50 kA value is the fuse breaking rating for VZFR-12/T160-50. It does not establish bare-switch breaking or withstand duties. Confirm the complete rating schedule for any other assembly; see the electrical ratings and service conditions.

03How should I choose the cabinet width?

Specify cabinet width, phase-centre spacing and pole spacing together. Match the dimensional schedule and complete outline with the approved cabinet layout. Use the cabinet dimensions for the selected VZFR-12 combination.

04What should I specify for the control circuit?

State AC or DC and the operating voltage, then confirm the charging motor, optional releases, auxiliary contacts and locks with the final schematic. The usual operating voltage is 220 V. See the mechanism and control selections.

05How should fuse links be selected for a VZFR-12 combination?

Start with the transformer or circuit duty, system voltage and fault level. Select the fuse type and current rating together with its dimensions, striker and tripping interface. Coordinate the fuse characteristics with the protected circuit and the complete switch-fuse assembly. See the fuse and cabinet-fit requirements.

06Which details are required to specify the assembly?

Provide the complete product designation and rating duties, cabinet fit, fuse specification for a combination, operating supply, auxiliary contacts and interlocks. Prepare the configuration requirements and complete the selection form.

Product engineering series