| 01 | Rated voltage | kV | 12 |
| 02 | Rated short-duration power-frequency withstand voltage (1 min) | kV | 42 |
| 03 | Rated lightning impulse withstand voltage (peak) | kV | 75 |
| 04 | Rated frequency | Hz | 50 |
| 05 | Rated current | A | 20 / 25 kA: 630, 1,250 31.5 kA: 630, 1,250, 1,600, 2,000, 2,500, 3,150 40 kA: 1,250, 1,600, 2,000, 2,500, 3,150, 4,000 |
| 06 | Rated short-circuit breaking current | kA | 20 / 25; 31.5; 40 |
| 07 | Rated short-time withstand current | kA | 20 / 25; 31.5; 40 |
| 08 | Rated short-circuit duration | s | 4 |
| 09 | Rated peak withstand current | kA | 20 / 25 kA: 50 / 63 31.5 kA: 80 40 kA: 100 |
| 10 | Rated short-circuit making current | kA | 20 / 25 kA: 50 / 63 31.5 kA: 80 40 kA: 100 |
| 11 | Secondary-circuit power-frequency withstand voltage (1 min) | V | 2,000 |
| 12 | Rated single / back-to-back capacitor-bank breaking current | A | 630 / 400 (40 kA version: 800 / 400) |
| 13 | Rated capacitor-bank switching inrush current | kA | 12.5 (frequency ≤ 100 Hz) |
| 14 | Opening time at rated voltage | ms | ≤ 50 |
| 15 | Closing time at rated voltage | ms | ≤ 60 |
| 16 | Mechanical endurance | operations | 10,000 |
| 17 | Rated-current interruption count (electrical life) | operations | 10,000 |
| 18 | Rated short-circuit current interruption count | operations | 50 (40 kA version: ≤ 30) |
| 19 | Permissible accumulated contact wear (moving / static) | mm | 3 |
| 20 | Rated closing-coil voltage | V | AC 110 / 220; DC 110 / 220 |
| 21 | Rated tripping-coil voltage | V | AC 110 / 220; DC 110 / 220 |
| 22 | Spring-charging motor rated voltage | V | AC 110 / 220; DC 110 / 220 |
| 23 | Spring-charging motor rated power | W | 70 |
| 24 | Spring-charging time | s | ≤ 10 |
| 25 | Contact gap | mm | 11 ± 1 |
| 26 | Contact overtravel | mm | 3.5 ± 0.5 |
| 27 | Contact closing bounce | ms | ≤ 2 (40 kA version: ≤ 3) |
| 28 | Three-phase closing / opening asynchronism | ms | ≤ 2 |
| 29 | Average opening speed | m/s | 1.1 ± 0.2 |
| 30 | Average closing speed | m/s | 0.6 ± 0.2 |
| 31 | Main-circuit resistance (fixed / withdrawable) | μΩ | 630 A: ≤ 45 / ≤ 60 1,250 A: ≤ 40 / ≤ 55 1,600–2,000 A: ≤ 30 / ≤ 50 2,500 A and above: ≤ 25 / ≤ 35 |
| 32 | Contact closing pressure | N | 20 kA: 2,000 ± 200 25 kA: 2,400 ± 200 31.5 kA: 3,100 ± 200 40 kA: 4,250 ± 250 |
| 33 | Rated operating sequence | | O – 0.3 s – CO – 180 s – CO |