12 kV series · Indoor isolation

GN19-12Indoor high-voltage disconnector

Three-pole arrangement shown. Match the mounting form, phase spacing and operating linkage to the approved order drawing.

No-load isolating switch for indoor 12 kV, 50 Hz systems. Choose the current and withstand combination, mounting form and manual operating arrangement for your panel.

Rated voltage
12 kV
Maximum voltage
12.5 kV
Rated frequency
50 Hz
Rated-current options
400–1,250 A
4 s thermal withstand
12.5–40 kA
Dynamic withstand
31.5–100 kA

Operate only with the circuit unloaded. Rated current and thermal / dynamic withstand values are paired by model; they do not define load-breaking capability.

GN19-12 technical specifications.

Choose a complete current and withstand combination, then match the installation form and site conditions. Operate the disconnector only with the circuit unloaded.

Common electrical ratings

Ratings for the GN19-12 and GN19-12C combinations below
No. Item Unit Value
01 Rated voltage kV 12
02 Maximum voltage kV 12.5
03 Rated frequency Hz 50

Model combinations

Current and withstand combinations
Model Rated current (A) 4 s thermal withstand (kA) Dynamic withstand (kA)
GN19-12/400-12.5 400 12.5 31.5
GN19-12/630-20 630 20 50
GN19-12/1000-31.5 1,000 31.5 80
GN19-12/1250-40 1,250 40 100
GN19-12C/400-12.5 400 12.5 31.5
GN19-12C/630-20 630 20 50
GN19-12C/1000-31.5 1,000 31.5 80
GN19-12C/1250-40 1,250 40 100

GN19-12 is the flat-mounted form; GN19-12C is the through-wall form. Thermal and dynamic withstand currents are paired with rated current by model and do not define load-breaking capability.

Service conditions

Indoor installation conditions
No. Item Unit Value
01 Altitude m ≤ 1,000
02 Ambient air temperature °C −30 to +40
03 Relative humidity at +20 °C % ≤ 90
04 Seismic intensity — ≤ 8
05 Installation environment — No fire or explosion hazard, severe pollution, chemical corrosion or violent vibration

For pollution-resistant W, high-altitude G or voltage-display X derivatives, confirm the derivative-specific rating and installation schedule. Agree any site conditions outside this envelope before ordering.

Mounting and operating options.

Match the flat-mounted, side-mounted or through-wall form to the panel. Specify the primary connections, operating direction and accessories together.

Installation arrangements

Arrangement Mechanical and primary fit Operating interfaces and accessories
Flat-mounted GN19-12 Match the phase spacing, fixing holes and primary-terminal layout to the panel. Left- and right-hand operation are usual. Specify upright or inverted blade orientation and the operating linkage.
Side-mounted GN19-12M Match the operating panel, frame fixing points and primary-terminal clearances. Specify left or right operation, upright or inverted mounting, and the matching socket and handle.
Through-wall GN19-12C Choose C1 blade side through the wall, C2 stationary-contact side, or C3 both sides. Specify the primary-conductor layout. Confirm the through-wall side and operating linkage on the complete assembly drawing.

Mounting and primary connections

Through-wall direction
C1: blade side through the wall; C2: stationary-contact side; C3: both sides. C1 is the usual selection. Match the wall opening and insulation clearances.
Through-wall connections
Upper-flat / lower-straight is usual. Flat-in / flat-out requires a custom assembly drawing.
Phase spacing and fixing points
Choose 190, 210, 250 or 275 mm phase spacing. Usual selection: 210 mm, with a 620 × 240 mm installation reference. Confirm the mounting pattern for the selected form.
Side-mounted panel
Panel: 135 × 185 mm. Usual references: 185 mm from the panel to the frame fixing hole and 495 mm from the B-phase centre to the panel. Confirm the exact interface drawing.
Primary phase order
Flat-mounted upright arrangement: A / B / C from left to centre to right. Confirm the terminal phase order for side-mounted or inverted arrangements.
Derivative construction
Specify GN19-12W(C) for pollution-resistant construction, GN19-12G(C) for high-altitude use, or GN19-12X(C) with a voltage-display device. Agree the derivative-specific ratings and installation schedule.

Operating mechanisms and accessories

Operating direction
Flat-mounted and through-wall forms are usually operable from either side. Side-mounted forms require a left- or right-hand choice; state the orientation on the order drawing.
Inverted mounting and holding spring
Blade-down inverted mounting requires an opening-position holding spring, including an inverted side-mounted assembly with an operating panel.
Manual mechanism
Specify no separate mechanism or a matched CS6 mechanism. JSXGN-12 is another manual operating interface to confirm with the assembly; side-mounted forms include the matching socket and handle.
Auxiliary switch
Omitted as usual. When required, specify the open / closed contact counts and terminal assignments.
Voltage-presence sensor
Omitted as usual. Choose stationary-contact-side or blade-side installation and confirm which primary terminal is the incoming side.
Earthing-blade requirement
An assembly with an integral earthing blade is identified as GN24. Specify the appropriate product and its interlocks instead of adding an earthing blade to the GN19-12 selection.

State the full model, quantity, rated current / withstand combination, installation form and manual mechanism. Confirm the assembly outline, wall or panel interface, phase order and operating sequence before ordering. Usual selections depend on the chosen form.

Outline and mounting dimensions.

Compare the flat-mounted, through-wall and side-mounted arrangements. Use the approved order drawing to confirm dimensions, units, tolerances and the selected arrangement.

Choose an installation drawing

Flat-mounted GN19-12

Open full-size drawing

GN19-12 flat-mounted front and side dimensional views.

Check the flat-mounted assembly, operating direction and cabinet clearances against the selected model.

Open installation drawing page

Through-wall GN19-12C1

Open full-size drawing

GN19-12C1 through-wall front and side dimensional views.

This arrangement shows the GN19-12C1 blade-side through-wall version. Confirm the selected C1, C2 or C3 arrangement and wall connections.

Open installation drawing page

Side-mounted GN19-12M

Open full-size drawing

GN19-12M side-mounted front and side dimensional views.

Confirm the side panel, operating direction and phase order. The 170 custom callout requires agreement on the ordered arrangement.

Open installation drawing page

A/B/C mounting dimensions

These callouts apply to the four listed 630 A and 1,250 A models. Confirm the exact assembly and mounting-hole detail on the approved order drawing.

Assembly dimensions by model
Model A B C · mounting-hole detail
GN19-12/630 455 460 4 × 14 × 24
GN19-12/1250 510 520 4 × 18 × 28
GN19-12C/630 410 690 4 × 14 × 24
GN19-12C/1250 465 780 4 × 18 × 28

Manual and selection form.

Use the manual and selection form to specify the mounting arrangement, operating linkage and accessories.

Available · PDF · 4 pages

GN19-12 indoor disconnector manual

Ratings, service conditions, GN19-12 and GN19-12C installation arrangements, operation and ordering details. Confirm the selected model and cabinet interfaces.

Available · DOC

GN19-12 selection form

Specify quantity, full model, mounting arrangement, phase spacing, operating direction, mechanism, auxiliary contacts and voltage-presence sensors. Confirm inverted-mounting spring requirements and the complete order drawing.

Price & quotation.

Configuration · GN19-12/630

GN19-12/630 indoor disconnector

Price reference for the specified GN19-12/630 configuration. 630 A three-pole disconnector. Other currents and operating arrangements are quoted separately.

Rated voltage
12 kV
Rated current
630 A
Poles
3

Price range

USD 140–150 / set

USD per complete three-phase set. Minimum order: 1 set. USD 150 per set for 1–99 sets; USD 140 per set for 100+ sets. Shipping and taxes are excluded. Other configurations and accessories require a separate quotation. Confirm the specification and final quotation before ordering.

The range reflects order-quantity tiers for this configuration; it does not cover every option in the series.

Quantity pricing
Published quantity tiers for this configuration
Quantity (sets) Price per set
1–99 USD 150
100+ USD 140

GN19-12 selection questions.

Answers about no-load isolation, mounting arrangements and ordering requirements.

01Which current and withstand combinations can I specify?

Specify the full model suffix. The listed current / 4 s thermal / dynamic combinations are 400 A / 12.5 kA / 31.5 kA, 630 A / 20 kA / 50 kA, 1000 A / 31.5 kA / 80 kA and 1250 A / 40 kA / 100 kA for GN19-12 and GN19-12C. These are paired withstand ratings. See the model rating schedule.

02Can GN19-12 interrupt load current?

GN19-12 is an indoor disconnector for isolation at voltage under no-load conditions. Its thermal and dynamic withstand ratings are not load-breaking or short-circuit interruption ratings. Coordinate circuit opening and isolation with the switchgear operating procedure.

03How do I select a through-wall arrangement?

GN19-12 is the flat-mounted version; GN19-12C is the through-wall family. C1 passes through the blade side, C2 through the stationary-contact side and C3 through both sides. Confirm wall connections, operating direction and clearances against the installation choices and selected outline.

04What is required for inverted mounting?

An inverted blade-down assembly requires an opening-holding spring. The spring is also required for an inverted side-mounted assembly with an operating panel. Confirm mounting direction, mechanism and operating access in the selection form before ordering.

05Can I order an integral earthing blade as a GN19-12 option?

The assembly with an integral earthing blade is designated GN24. Specify the correct product identity and confirm the complete arrangement; do not treat it as a GN19-12 configuration. See the installation and operating options.

06What should accompany a quotation request?

Provide quantity, complete model, mounting arrangement, phase spacing, operating direction and mechanism selection, including any auxiliary contacts or voltage-presence sensors. For a side-mounted assembly, confirm the handle and sleeve. Use the approved order drawing to confirm dimensions, units, tolerances and interfaces. Complete the selection form with the required arrangement.