24 kV series · Indoor switchgear

VS1-24Indoor vacuum circuit breaker

Side-mounted arrangement shown. Match mounting points, pole spacing and control terminals to the approved order drawing.

Spring-operated breaker for 24 kV, 50 Hz indoor switchgear. Specify the current and breaking-duty combination, mounting arrangement, cabinet interfaces and operating supply.

Rated voltage
24 kV
Rated frequency
50 Hz
Rated-current range
630–3,150 A
Breaking duties
25 / 31.5 kA
Arrangement shown
Side-mounted
Mechanical life
10,000 operations

The 3150 A rating uses the 31.5 kA combination. Match each current, breaking duty and mounting arrangement to the approved assembly.

VS1-24 technical specifications.

Match the rated current and breaking duty first, then check the mounting arrangement, operating characteristics and site conditions.

Electrical ratings

24 kV · 50 Hz indoor vacuum circuit breaker
No.ItemUnitValue
01Rated voltagekV24
02Rated frequencyHz50
03Power-frequency withstand, phase-to-earth (1 min)kV65
04Power-frequency withstand, across open gap (1 min)kV79
05Lightning-impulse withstand, phase-to-earth (peak)kV125
06Lightning-impulse withstand, across open gap (peak)kV145
07Rated current at 25 kA breaking dutyA630 · 1,250 · 1,600 · 2,000 · 2,500
08Rated current at 31.5 kA breaking dutyA630 · 1,250 · 1,600 · 2,000 · 2,500 · 3,150
09Rated short-circuit breaking currentkA25 / 31.5
10Rated short-time withstand current (4 s)kA25 / 31.5
11Rated short-circuit making current (peak)kA63 / 80
12Rated peak withstand currentkA63 / 80
13Rated short-circuit breaking operationsoperations> 20
14Rated operating sequence—O–0.3 s–CO–180 s–CO
15Auxiliary-circuit power-frequency withstand (1 min)V2,000

The 63 / 80 kA peak values correspond to the 25 / 31.5 kA breaking duties. The 3,150 A option uses the 31.5 kA combination. Confirm duties outside these combinations for the exact ordered assembly.

Mechanical characteristics

Operating characteristics and main-circuit resistance
No.ItemUnitValue
01Mechanical lifeoperations10,000
02Phase centre distancemm275 ± 1.5
03Contact gap, standard dutymm15 ± 1
04Contact gap, 3,150 A / 31.5 kAmm12 ± 1
05Contact-pressure spring travel, standard dutymm3.5 ± 0.5
06Contact-pressure spring travel, 3,150 A / 31.5 kAmm3.5 ± 1
07Three-phase closing / opening asynchronismms< 2
08Closing bounce timems< 3
09Closing timems35–70
10Opening timems20–50
11Closing speedm/s0.6–1.1
12Opening speedm/s1.1–1.6
13Main-circuit resistance, 630 AμΩ< 55
14Main-circuit resistance, 1,250 AμΩ< 45
15Main-circuit resistance, 1,600 / 2,000 AμΩ< 35
16Main-circuit resistance, 2,500 / 3,150 AμΩ< 25

The 3,150 A / 31.5 kA contact gap and spring travel differ from the standard-duty values. Match the phase spacing and mounting dimensions to the approved cabinet drawing.

Service conditions

Indoor operation and storage / transport
No.ItemUnitValue
01Ambient temperature in operation°C−15 to +40
02Minimum storage / transport temperature°C−25
03Altitudem≤ 1,000
04Relative humidity, daily mean%≤ 95
05Relative humidity, monthly mean%≤ 90
06Water-vapour pressure, daily meankPa≤ 2.2
07Water-vapour pressure, monthly meankPa≤ 1.8
08Seismic intensity—≤ 8
09Site contamination—No significant dust, smoke, corrosive or flammable gases / vapours, or salt-mist pollution
10Induced voltage in the secondary circuit (peak)kV≤ 1.6

Specify any site condition outside this envelope before ordering, so the equipment and installation requirements can be agreed.

Installation and control options.

Choose the mounting arrangement and complete current / breaking-duty pair, then specify the cabinet dimensions, interlocks and control circuit.

Installation arrangements

ArrangementMechanical and primary fitControl and interlocks
Withdrawable handcartCommon combinations: VS1-24/630-25, /630-31.5, /1250-25 and /1250-31.5. Match cabinet width, carriage guides and primary contacts to the ordered duty.Confirm the racking and grounding interfaces, operating supplies and auxiliary-contact reserves.
Fixed assemblyConfirm the exact 24 kV assembly, rating pair, fixing points and primary connections on an assembly-specific outline.Specify operating access, secondary wiring and the required cabinet interlocks.
Side-mounted630 / 1250 / 1600 A arrangements use 230 / 275 mm phase spacing, 310 mm pole spacing and a 380 mm front width. Match the exact current / breaking-duty pair.Specify cable-exit direction, top and main-shaft interlocks, supplies and auxiliary-contact reserves.

Cabinet and primary interfaces

Handcart cabinet and phase spacing
Usual handcart selections: 800 mm cabinet / 210 mm phases for 1600 A and below; 1000 mm / 275 mm above 1600 A. The illustrated 275 mm arrangements use a 1000 mm cabinet, including lower currents; confirm the complete outline.
Handcart pole spacing
Usual selections: 275 mm for the 800 mm cabinet and 310 mm for the 1000 mm cabinet. Match the phase and pole spacing independently.
Side-mounted geometry
Specify 230 or 275 mm phase spacing, 310 mm pole spacing and a 380 mm front width on the ordered outline.
Insulation construction
Conventional insulating cylinders are usual; sealed poles are an option. The handcart 65 kV phase-to-earth / 79 kV open-gap withstand selection uses the standard 24 kV sealed-pole construction. Confirm the full insulation schedule.
Handcart grounding
Bottom friction grounding is usual; side grounding clamps are an option. Match the grounding arrangement and contact positions to the cabinet.
Operating mechanism
Spring operation is usual. For a permanent-magnet handcart mechanism, agree the matching operating circuit and mechanical schedule.
Side-mounted cable exit
Choose left or right cable exit and confirm clearance at the primary connections.

Control and order details

Operating supplies
110 V or 220 V AC/DC; 220 V is usual. A 48 V side-mounted supply requires the matching circuit. State closing, tripping and charging supplies separately.
Auxiliary-contact reserves
Handcart: 4 NO / 4 NC. Side-mounted: 6 NO / 5 NC. Spare spring-charging contacts: 2 NO / 1 NC. Specify any additional contacts and confirm terminal assignments.
Anti-pumping and locking
Anti-pumping is usual. Closing and handcart-racking solenoid locks are options; specify the required locking functions.
Overcurrent coils
Normally omitted. When required, specify coil quantity and rated current with the operating circuit.
Side-mounted top interlock
Choose left, right or no opening interlock. Usual selection: right-hand extension, 50 mm.
Side-mounted main-shaft interlock
Choose left, right or no projection beyond the frame. Usual selection: right-hand extension, 50 mm.
Handcart key interlocks
Specify two locks / one key or three locks / two keys and agree the operating sequence.
Additional handcart duties
Specify undervoltage / loss-of-voltage tripping and any capacitor-switching duty or associated conditioning-test requirement.
Side-mounted control board
Usual selection: AC/DC board. Specify a circuit without semiconductors and diodes when required, with the matching wiring schedule.
Panel, documents and packing
Specify bilingual or English panels, document and label language, frequency marking consistent with the ordered rating, and any export-type unmarked wooden case.

State the full model, quantity and arrangement with the cabinet outline and terminal schedule. Confirm duties beyond 25 / 31.5 kA, non-standard supplies or other operating frequencies for the exact assembly and applicable technical documents.

VS1-24 · CABINET INTERFACE

Primary-contact dimensions.

Use these contact diameters to plan the cabinet interface. Confirm rated current, breaking current and mounting arrangement together on the approved order drawing before panel layout.

630–1,600 A range

Recommended for a 1,000 mm cabinet
Rated currentBreaking currentContact diameter D
630 A25 / 31.5 kA35 mm
1,250 A25 / 31.5 kA49 mm
1,600 A25 / 31.5 kA55 mm

1,600–3,150 A range

Recommended for a 1,000 mm cabinet
Rated currentBreaking currentContact diameter D
1,600 A25 / 31.5 kA79 mm
2,000 A25 / 31.5 kA79 mm
2,500 A25 / 31.5 kA109 mm
3,150 A31.5 kA109 mm
15–25 mm

Contact-fit dimension L

Verify final contact engagement against the approved order drawing.

Product documents.

Review the manual for ratings, service conditions and structure references. The sample report below addresses insulation tests for its named configuration.

Cover of the VS1(ZN63)-24 indoor vacuum circuit breaker manual.

Available · PDF

VS1(ZN63)-24 product manual

Product ratings, service conditions, mechanism and installation references for the VS1-24 series.

Open manual PDF

On request · sample report

VS1-24/1250-31.5 insulation test report

Report DG22050197, dated 30 June 2022, records power-frequency, lightning-impulse and auxiliary-circuit insulation tests for the VS1-24/1250-31.5 sample. It does not include short-circuit interruption, endurance or temperature-rise test results.

Request the sample report

See Liqiang manufacturing and inspection activities. Model reports and factory inspection records serve different purposes; match the required documents to the proposed equipment.

Price & quotation.

Configuration · ZN63-24/630-31.5

ZN63-24/630-31.5 side-mounted indoor vacuum circuit breaker

Price reference for the specified ZN63-24/630-31.5 configuration. VS1/ZN63 side-mounted arrangement; phase spacing and operating supply must be confirmed.

Rated voltage
24 kV
Rated current
630 A
Short-circuit breaking current
31.5 kA
Arrangement
Side-mounted

Price range

USD 1215–1220 / set

USD per complete three-phase set. Minimum order: 1 set. USD 1220 per set for 1–9 sets; USD 1215 per set for 10+ sets. Shipping and taxes are excluded. Other configurations and accessories require a separate quotation. Confirm the specification and final quotation before ordering.

The range reflects order-quantity tiers for this configuration; it does not cover every option in the series.

Quantity pricing
Published quantity tiers for this configuration
Quantity (sets)Price per set
1–9USD 1220
10+USD 1215

VS1-24 · Product selection

Frequently asked questions.

Check ratings, installation fit and order details before finalizing your panel design.

01Which rated-current and breaking-current combinations are listed?

The ratings table lists 25 kA at 630, 1,250, 1,600, 2,000 and 2,500 A; 31.5 kA is listed at those currents and at 3,150 A. Check the chosen mounting form for the exact orderable combination in the ratings table.

02How do I choose between the 25 kA and 31.5 kA options?

Use the prospective short-circuit current at the installation point to select the breaking-current rating. Select the continuous-current rating for the load separately, and check the corresponding withstand and making duties. The VS1-24 ratings table lists the available current and breaking-duty combinations.

03Which mounting arrangements are available?

Specify withdrawable or side-mounted construction to suit the cabinet. For a fixed 24 kV assembly, confirm the complete model code, mounting dimensions and control interfaces on the approved order drawing. Review the configuration details.

04Which site conditions matter when selecting a VS1-24?

Include altitude, ambient-temperature range, humidity, condensation and dust or corrosive exposure in the enquiry. These conditions affect the insulation and operating environment inside the switchgear. Compare them with the service conditions and identify any special requirements before choosing the breaker and cabinet arrangement.

05Which control-supply options should I specify?

The withdrawable selection lists 220 V AC/DC as standard; AC/DC 110 V and 220 V are also listed for ordering. Specify closing, tripping and spring-charging supplies separately in the configuration details.

06What information is needed for a cabinet-fit review?

Provide the model and rated-current / breaking-current pair, mounting form, cabinet outline, phase and pole spacing, primary contact dimensions, control supply and auxiliary-contact requirements. For replacement work, include the existing nameplate and interface photos. Compare the cabinet interface dimensions with the approved order drawing.

Product engineering series

About Liqiang

Manufacturing and technical support.

Technical selection guide